Bus parameters
10.6
Bus parameters
In the
Bus parameters
area, you can set the address of the
KBR eBus
, for example.
1.
From the
main menu, select Bus parameters > Enter
.
2.
If necessary, start a bus scan using
scan
.
3.
Begin programming by selecting
Edit
.
If you have selected the protocol Modbus RTU, proceed as follows:
The device will reboot after switching to Modbus.
1.
From the
main menu, go to Bus parameters > Enter
again.
2.
Begin programming the bus address by selecting
Edit
.
3.
Select the baud rate and then the protocol type (mode) from (4800, 9600, 19200, 38400
or RTU Parity none, even, odd)
Bus Param-
eters
Bus protocol
KBR eBus / Modbus
Bus address KBR
eBus
0 to 9999 configurable on the device, scanning
mode
Bus address
Modbus
1 to 247 configurable on the device
Transmission
speed
Can choose 4800, 9600, 19200, 38400 baud
Protocol type
RTU Parity none, even, odd