V5.00
25832_EDEBD
A0289-5020-1_EN
48
Line parameters
Para Lines
(1, 2, ...)
Programming
Explanation
Feedback
type
Enable,
Manual_Off,
Manual_On,
Emergency_Off,
Emergency_On,
priority 1–32
Defines whether the device is integrated into
optimization via its feedback (enable), remains
constantly on (Manual_On), or is switched off in-
dependently of its trend calculation (Manual_Off).
In the case of running timer programs, there is
an additional option to modify the process and
influence the state of the optimization lines:
Emergency_On (switches on the line in case of
emergency)
Emergency_Off (switches off the line in case of
emergency)
The current line priority can also be changed
Pact
Adr.
Input
I...
Message input address via which the current
device power consumption is established using
a power measurement module or analog input
module.
Switch off
in event of
error
On/Off
Defines whether the device is switched off
in event of error.
Power on
state
On/Off
Determines the line state when the power returns
after a power failure
Line group 0 to 65535
Line assignment to a line group
The following errors can trigger an emergency shut-down:
the cumulated measurement period power is greater than the target value
the “maximum current power” limit has been exceeded
Meter 1 meter pulse failure
Meter 2 meter pulse failure
Meter 3 meter pulse failure
Meter 4 meter pulse failure
Meter 5 meter pulse failure