V5.00
25832_EDEBD
A0289-5020-1_EN
47
Line parameters
3.
Program the address with
Adr
and
Edit
.
Para Lines
(1, 2, ...)
Programming
Explanation
Adr.
output
Numeric value
O01–O32,
fixed
Device address, O01–O04 on the base device;
afterwards, numbering is continued for connected
modules.
Adr.
feedb.
I00-I50
The multimax checks whether the device is on or
off and sends a message about this via the feed-
back input. If this does not occur, the multimax
switches regardless of whether the device is on
or off and then waits the set time until the next
switching event.
NOTE
In addition to the digital input module inputs (for floating switches or electronic switches
(ensure correct polarity)), the voltage inputs of the
multimess D4-1 measurement module can also be used as feedback inputs. With this
module, 230 VAC feedback messages (e.g. directly from the device main switch) can be
evaluated. An input voltage of > 70 VAC is evaluated as an on state.
4.
Program the device’s time-dependent parameters
with
Time
and
Edit.
Line times
(1, 2, etc.)
Program-
ming
Explanation
Per. Time-out
Numeric
value
in
min
Defines the time that the device stays on
from the start of the period under all circumstanc-
es.
Lead time
Numeric
value
in
sec
Defines the lag time for turning the device on – the
device only reaches its power after this time.
Run-on time
Numeric
value
in
sec
Defines the lag time for turning the device off – the
device power only reaches zero after this time.
Minimum on time/
day
Numeric
value
in
hrs
Minimum time period for which the device
must be switched on per day
Min. On Min. Off
Max. Off
Numeric
value
in
min
Minimum time period for which the device may
be switched on or max./min. time period for which
the device may be switched off in relation to a
period.