Line parameters
The line output power only changes in the switching cycle: once the output power has
changed, it will not be changed again for the duration of the switching cycle.
Once output power reaches 0 or 100%, the next line is switched to (depending on the
line priority). This is also the case for circular switching (lines with the same priority).
The following parameters are considered:
Minimum off time:
Takes effect when the output power has reached zero.
Minimum on time:
Takes effect when the output power is greater than zero. The output power can then
not be reduced until the minimum on time has elapsed.
Additional notes:
On/off state:
When the output power is zero, then the state is “Off.”
Otherwise, the state is “On.” Switching reasons that switch the line on or off switch the
power to 100% or 0% (e.g. Manual On/Manual Off). The period time-out switches the out-
put power to 100%. Timer programs can currently only switch the analog lines off (0%) or
on (100%). In the switching operations memory, only a change from 0% to greater than
0% and vice-versa is logged.
The following parameters are available:
1. Module name (module no., output no.)
2. Logical address O01 (example) to O32
3. Type: 10 V or 20 mA
4. min. value kW (+/-)
5. max. value kW (+/-)
6. Min. output value: 0 V or 0 mA
7. Max. output value: 10 V or 20 mA
8. Default value (output): 0 V or 0 mA
9. Edge (gradient) in milliseconds
Explanation:
Default value = output when power returns after power failure
Edge = change in output value in milliseconds (jump from min. to max.)