English
15
1 Display
2 ADVANCE key
During operations, the current time is
shown in the display.
Î
Press ADVANCE key for 5 to 6 sec-
onds. The display will show the first sta-
tus display from the list shown beloe.
Î
To go to the next display, press once
again the ADVANCE key briefly.
If you do not press the ADVACE key for
some time, the display goes back to show-
ing the time.
The dosing pump must be dearated if the
pump has sucked in air (for e.g. if the dos-
ing container has been completely emp-
tied).
– The unit will stop; the display shows the
interruption "Motor protection".
Note
This errror message is displayed independ-
ent of which dosing container has been
used.
1 Dosing frequency button
2 Screw connections
3 Dosing pump
Î
Refill dosing station (refer chapter on
Startup)
Î
Loosen screws on the dosing pump.
Î
Read and note the dosing frequency
that has been set at the LEDs of the
dosing pump.
Î
Set the dosing frequency to 100% by re-
peatedly pressing the dosing frequency
button and waiting until there are no
more bubbles in the suction pipe (ap-
prox. 1 minute). Absorb the oozing dos-
ing liquid with a piece of cloth.
Î
Tighten the screws.
Î
Set the dosing pump to the original dos-
ing frequency.
1 Return key
Î
Accept the interruption message on the
operating panel by pressing the Return
key; the unit will start.
Î
Check the pressure difference between
the two manometers. Change filter inlay
if value is more that 0.08 MPa (0.8 bar):
Î
Turn the main switch to position "0"
Î
Interrupt raw water inflow.
Î
Open the raw water testing tap to de-
pressurise the filter.
Maintenance schedule
Time
Check / Activity
Target value
In case of deviation
daily
Filling level of dosing container
adequate filling
refill
Air bubbles in the dosing pipes
no air bubbles
Bleed dosing pump.
Drinking water flow based on the startup value Lowered by less than 10%
Fine regulation
Drinking water guide value based on the start-
up value
Increase within 10%
Fine regulation
Pressure difference between pump and con-
centrate pressure
maximum 15% above startup difference
Kärcher Customer
Service
Counter/meter for media and active carbon fil-
ters
Reflushing has taken place in the last 24 hours Kärcher Customer
Service
Pressure difference fine filter
maximum 0.08 MPa (0.8 bar)
Replace fine filter
Visual inspection of the plant
no leaks
Kärcher Customer
Service
weekly
Fill up operations log
monthly
Clean and rinse dosing container
Visual inspection of raw water pump
No damage/ leaks can be detected
Kärcher Customer
Service
Float switch in drinking water tank
no functional disruption can be detected
Kärcher Customer
Service
Maintenance Works
Check media and active carbon filters
Display
Significance
2000
Not important
0000
Not important
D–07
Number of days until the
next reflushing
–001
Number of reflushing that
have been conducted
0–01
days - hours since the last
reflushing
Bleed dosing pump.
Replace fine filter
Summary of Contents for WPC 10000 BW-AM
Page 2: ......
Page 12: ...12 Deutsch R ckseite Bleibt leer damit das Blatt herausgetrennt werden kann...
Page 22: ...22 English Rear side Is kept blank so that the sheet can be separated...
Page 32: ...32 Fran ais Verso Reste vide afin que la feuille peut tre retirer...
Page 44: ...44 Italiano Tergo Resta vuoto in modo da poter separare il foglio...
Page 54: ...54 Nederlands Achterkant Blijft leeg zodat de pagina eruit gehaald kan worden...
Page 64: ...64 Espa ol Parte posterior En blanco para separar la hoja...
Page 66: ...66 IEC 60364 1 3 m 1 _ _ _ _ _h_ _min 14 K rcher 0 K rcher...
Page 71: ...71 LED K rcher 5 RO LED fault regeneration tank full LW...
Page 74: ...74 WPC A 1 024 h dH S cm pH pH C MPa MPa MPa MPa MPa MPa MPa MPa MPa l h l h S cm K rcher...
Page 76: ...76...
Page 86: ...86 T rk e Arka sayfa Sayfan n ayr labilmesi i in bo kal r...
Page 88: ...88 cc 5 C IEC 60364 1 3 1 _ _ _ _ _ _ _ 14 K rcher 0 rcher...
Page 93: ...cc 93 RO K rcher 5 RO LW...
Page 96: ...96 cc WPC A 1 024 dH pH pH C M a M a M a M a M a M a a a a Antiscalant rcher...
Page 97: ...cc 97 WPC B 1 024 C a 1Pr04 a 1Pr05 a 1Pr 06 1Fl01 1Fl03 1Fl02 ____...
Page 98: ...98 cc...