23 of 32
© 2003
D 369e - 06/03
Misc
(Miscellaneous)
Menu (1 of 1)
°
F,
°
C
Default =
°
C
OFF, 30 sec, ON
Default = ON
ADV, INST, USER, LTD
Default = INST
LTD
INST ADV
USER
Item Field
Description
Access
Level
Range
The operating mode for the backlighting on the LCD as well
as the time of keypad inactivity until the control automatically
returns to the default display.
BACKLITE = OFF
(returns after 10 seconds)
BACKLITE = 30 sec
(returns after 30 seconds)
BACKLITE = ON
(returns after 90 seconds)
The access level that is to be used by the control.
DIP switch =
Unlock
The units of measure that all of the temperatures are to be
displayed.
Room Temperature Units (RTUs) 062e and 063e
A display RTU may be connected to the Zone Control 369e in order to provide the control with indoor
temperature feedback for the heating system. When using display RTUs, several items related to the
system are no longer available in the control’s User Interface. These items are available only in the
RTU’s User Interface. Also, the number of items that are available on the RTU depends on the type of
RTU that is connected to the control.
RTU
View
Menu (1 of 1)
RTU 062e
RTU 063e
USER
– – –, 20 to 120
°
F
(– – –, -7 to 49
°
C)
– – –, 20 to 120
°
F
(– – –, -7 to 49
°
C)
– – –, 35 to 100
°
F
(– – –, 2 to 38
°
C)
-67 to 140
°
F
(-55 to 60
°
C)
-40 to 158
°
F
(-40 to 70
°
C)
D
D
D
D
D
Section
LTD
INST
ADV
Range
Access
Level
Description
Item Field
Average temperature of all the zones assigned to
the cooling group.
COOL MODE = CTRL and RTU 6
Current slab (floor) sensor temperature.
REMOTE 3 = FLOR
Current room air temperature.
Current outdoor air temperature.
Target room air temperature.