Document the control for future reference. Before making any adjustments to the control, note down
all of the items that the control is currently displaying. This includes items such as error messages,
current temperatures and settings, and which devices should be operating as indicated by the LCD.
This information is an essential step if additional assistance is required to diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is
known and the system is sketched, is the control operating the proper pumps and valves at the cor-
rect times? Is the control receiving the correct signals from the system as to when it should be oper-
ating? Are the proper items selected in the menus of the control for the device that is to be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving ade-
quate voltage to the power terminals and the demand terminals as noted in the technical data. Use
the multimeter to determine if the internal contacts on the control are opening and closing correctly.
Follow the instructions in the Testing the Wiring section to simulate closed contacts on the terminal
blocks as required. Test the sensors and their wiring as described in the sensor Data Brochures.
Monitor the system over a period of time. Select the application items in the Monitor menu of the con-
trol and reset them to zero. Allow the system and the control to operate over a known period of time
and then record the Monitor items. Use this information to help diagnose any remaining problems.
Monitor the
System
Document the
Control
Isolate the
Problem
Test the Con-
tacts, Voltages
and Sensors
Error
Messages (1 of 3)
Error Displayed
Description of Error
The control was unable to store a piece of information into its EEPROM. This error can be caused
by a noisy power source. The control will display the error message and will continue to operate
normal. Pressing either the
Menu
or
Item
button will clear this error.
The control was unable to read a piece of information stored in the Adjust menu. Because of this,
the control was required to load the factory settings into all of the items in the Adjust menu. The
control will stop operation until all of the items available in the Adjust menu of the control have
been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Monitor menu. Because of
this, the control was required to load the factory settings into all of the items in the Monitor menu.
The control will continue to display the error message until all of the items available in the Monitor
menu of the control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Schedule menu. Because of
this, the control was required to load the factory settings into all of the items in the Schedule
menu. The control will continue to display the error message until all of the items available in the
Schedule menu of the control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Miscellaneous menu. Because
of this, the control was required to load the factory settings into all of the items in the
Miscellaneous menu. The control will continue to display the error message until all of the items
available in the Miscellaneous menu of the control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.