RTU
Schd
(Schedule) Menu (1 of 1)
RTU 062e
RTU 063e
USER
7DAY, 24hr
Default = 7DAY
NONE, ZONE, CTRL
Default = NONE
NONE, ZONE, CTRL
Default = NONE
NONE, STRT, STOP,
BOTH
Default = BOTH
NONE, TMPY Occ Ovr,
PERM Occ Ovr, TMPY
UnOcc Ovr, PERM
UnOcc Ovr, HOL Ovr
Default = NONE
NONE, TMPY Occ Ovr,
PERM Occ Ovr, TMPY
UnOcc Ovr, PERM
UnOcc Ovr, HOL Ovr
Default = NONE
C
C
C
C
C
C
Section
LTD
INST
ADV
Range
Access
Level
Description
Item Field
The type of setback override that is in effect for all
schedules.
DIP switch =
Setback
HOL is available even if
DIP switch
≠
Setback
The type of setback override that is in effect for
this zone's schedule.
Note:
NONE, TMPY Occ
Ovr and PERM UnOcc Ovr is available in the LTD
access level.
DIP switch =
Setback
The schedule this zone uses for heating.
DIP switch =
Setback
Enables or disables the Optimum Start / Stop
feature for this zone.
DIP switch =
Setback
(Any air sensor on)
Selects the same schedule for each day of the week,
or a separate schedule for each day of the week.
DIP switch =
Setback
The schedule that is to be used for the cooling system.
COOL MOD
≠
NONE, RTU 6 and
DIP switch =
Setback
If the 7DAY/24h adjustment is set to 7DAY, the schedule listed below for SATURDAY is also available for SUNDAY. MONDAY,
TUESDAY, WEDNESDAY, THURSDAY and FRIDAY.
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
– –:– – to 11:50 PM or
– –:– – to 23:50
Default = – –:– –
C
C
C
C
C
C
C
C
Time when the second unoccupied period begins
every day.
7DAY/24h = 24hr and DIP switch =
Setback
Time when the second occupied period begins
every day.
7DAY/24h = 24hr and DIP switch =
Setback
Time when the first unoccupied period begins
every day.
7DAY/24h = 24hr and DIP switch =
Setback
Time when the first occupied period begins on
Saturday.
7DAY/24h = 7DAY and DIP switch =
Setback
Time when the first unoccupied period begins on
Saturday.
7DAY/24h = 7DAY and DIP switch =
Setback
Time when the second occupied period begins on
Saturday.
7DAY/24h = 7DAY and DIP switch =
Setback
Time when the second unoccupied period begins
on Saturday.
7DAY/24h = 7DAY and DIP switch =
Setback
Time when the first occupied period begins every day.
7DAY/24h = 24hr and DIP switch =
Setback
Occ 1
Occ 2
UnOcc 2
Occ 1
UnOcc 1
Occ 2
UnOcc 2
UnOcc 1
For an example on how to set a schedule, refer to the Example given in the Schedule menu of the 369e.
Note:
To skip an event
during a schedule, select the “Null” event. Use the arrow keys to select the “Time” between 11:50 PM and 12:00 AM. “– –:– –” is
displayed indicating that the event will not occur during the schedule.