MULTICAL® 402
Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016
29
5
Pressure loss
Pressure loss in a flow sensor is stated as max. pressure loss at q
p
The pressure loss in a sensor increases with the square of the flow and can be stated as:
. According to EN 1434 max. pressure loss
must not exceed 0.25 bar, unless the energy meter includes a flow controller or functions as pressure reducing
equipment.
p
kv
Q
∆
×
=
where:
Q = volume flow rate [m³/h]
kv = volume flow rate at 1 bar pressure loss [m³/h]
∆
p = pressure loss [bar]
Graphs
qp
Nom. diameter
kv
[
m³/h
]
[mm]
[
m³/h
]
A
0.6 & 1.5
DN15…DN20
3
1.5
B
2.5 & 3.5 & 6
DN20 & DN25
13.5
6.8
C
10 & 15
DN40 & DN50
43
21.7
Table 5: Pressure loss table
Diagram 2: Pressure loss graphs
0,01
0,1
1
0,1
1
10
100
∆
p [
ba
r]
Flow [m³/h]
∆
p MULTICAL
®
402
A
B
C