12. Control PCB Parameter List
Function
Settings
Min Max
Unit
Comment
P000
Software version (read-only)
0
255 -
P001
Base setpoint for setpoint entry ± 3K
32
8
32 °C
P002
Switching on / off hysteresis valves
1
0
255 °C/10
P003
Neutral zone in a 4-pipe system
3
0
255 °C/10
P004
Cooling without fan support
0
0
255 °C/10
P005
Heating without fan support
3
0
255 °C/10
P006
Hysteresis fan On/Off
(ventilation-only mode)
5
0
255 °C/10
P007
P-band for heating
17
0
100 °C/10
P008
P-band for cooling
20
0
100 °C/10
P009
Offset to the base setpoint for
Setpoint input +/- 3K
0
0
10 °C
P010
Clip-on sensor:
Limit value temperature to activate
fan stages 1 and 2 in heating mode
29
0
255 °C
P011
Clip-on sensor:
Limit value temperature to activate
fan stages 3 and 4 in heating mode
31
0
255 °C
P012
Clip-on sensor:
Limit value temperature to activate
fan stage 5 in Heating mode
33
0
255 °C
P013
Clip-on sensor:
Hysteresis for limit value temperatures
P010, P011, P012, P014
10
0
255 °C/10
P014
Clip-on sensor:
Limit value temperature to activate
fan stages in Cooling mode
18
0
255 °C
P015
Function of input AI1
0
0
19 -
P016
Function of input AI2
0
0
19 -
P017
Function of input AI3
0
0
9 -
P018
Raising the cooling setpoint in
Eco mode
30
0
255 °C/10
P019
Lowering the heating setpoint in
Eco mode
30
0
255 °C/10
P020
Default value must be set
6
0
15 -
P021
Default value must be set
6
0
15 -
P022
Default value must be set
0
0
1 -
P023
Default value must be set
0 -99
127 °C/10
P024
Default value must be set
0 -20
20 01.10.12
P025
Default value must be set
0 -99
127 °C/10
P026
Default value must be set
0 -20
20 01.10.12
P027
Fan setting: Maximum running time of manual
Fan mode
0
0
255 minutes
P028
Rinsing function: Fan stage during rinsing
function
2
1
5 -
P029
Continuous fan operation
1
0
1 -
P030
Default value must be set
12
0
255 °C
P031
Default value must be set
27
0
255 °C
P032
Rinsing function: Maximum idle time of fan
15
0
255 minutes
P033
Rinsing function: Duration of rinsing function
240
0
255 S