
Ka
Control
for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
45
Door air curtains
1.96
Function
Settings
Min Max
Unit
Comment
P098
Actuation 0..10V: Switching on limit
Valves
30
0
100 V/10
P099
Actuation 0..10V: Switching on limit
Minimum fan speed
40
0
100 V/10
P100
Actuation 0..10V: Switching on limit
Maximum fan speed
90
0
100 V/10
P101
Valve actuation by means of pulse width modulation
P-band in Heating mode
15
0
100 °C/10
P102
Default value must be set
15
0
100 °C/10
P103
Valve actuation by means of pulse width
modulation
Reset time of PI controller
If P103=0 a PI controller is enabled.
Recommended reset time when using a PI
controller: Reset time = 13 minutes
0
0
20 minutes
P104
Valve actuation by means of pulse width modulation
Minimum switching on time for the heating value in
PWM mode
0
0
20 minutes
P105
Default value must be set
50
0 --
-
P106
Default value must be set
50
0 -
-
P107
Default value must be set
5
0
255 minutes
P108
Default value must be set
240
35
255 minutes
P117
Function buttons: Locking and enabling
0
0
7 -