Ka
Control
for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
25
Door air curtains
1.96
9 Setting Configuration of Unit by Means of DIP Switch
Set the configuration of a door air curtain using the DIP switch on the
PCB.
Once the DIP switch has been set, all the basic functions of the
configuration have been parameterised and the door air curtain can
be operated immediately.
Special setting options have to be parameterised in the Service menu.
This parameterisation is possible using the KaController.
Open the control unit to check and possibly adjust the DIP switches.
The DIP switches are factory-set in accordance with the unit
configuration!
Disconnect the control before starting to adjust the
DIP switches.
DIP switch settings on the PCB
DIP1
OFF =
ON =
-----
Actuation by means of a measurement and control system
provided by others
DIP2
OFF =
ON =
It is essential that DIP switch no. 2 is set to OFF
-----
DIP3
OFF =
ON =
No clip-on sensor fitted
Clip-on sensor fitted
DIP4
OFF =
ON =
Summer mode / winter mode changeover by KaController
Summer mode / winter mode changeover by DI2
DIP5
OFF =
ON =
It is essential that the DIP switch is set to OFF
-----
DIP6
OFF =
ON =
Temperature detection by induction sensor/ ext. room sensor
Temperature detection by KaController
DIP switch
PCB