INSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATION AND OPERATING INSTRUCTIONS
1.96
38
Door air curtains
11.3.5.2 Function of AI2
Parameter P16
Parameter PI6 is used to set the function of the multifunctional input AI2.
The multifunctional input AI2 can only be set using parameter P16 if DIP switch no. 3 is set to OFF!
The setting of DIP switches is described in section 10.
Function
Standard Min
Max Unit
P16
Function of Al2: see P15
0
0
19
11.3.5.3 Function of AI3
Parameter P17
Parameter PI7 is used to set the function of the multifunctional input AI3.
The multifunctional input AI3 can only be set using parameter P17 if DIP switch no. 3 is set to OFF!
The setting of DIP switches is described in section 10.
The multifunctional input AI3 can only process analog signals unlike inputs AI1 and AI2.
Function
Standard Min
Max Unit
P17
Funktion AI3
0
0
9
0 = Function of AI3 not used (input disabled)
1 = NTC Fresh air sensor
2 = NTC Cold / hot water sensor (clip-on sensor)
3 = NTC Cold water sensor (clip-on sensor)
4 = NTC Hot water sensor
5 = NTC External room temperature sensor / inlet air sensor
6 = 0..100 kOhm Fan actuation
7 = 0..100 kOhm Temperature setpoint
8 = 0..10 V BMS-Heating/cooling control
9 = 0..10 V BMS-Heating control