Ka
Control
for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
43
Door air curtains
1.96
Function
Settings
Min Max
Unit
Comment
P034
Rinsing function: Activation in operating modes
0 = Rinsing function disabled
1 = Rinsing function is enabled in:
- Cooling mode
- Automatic mode
Rinsing function is enabled in:
- Heating mode
- Automatic mode
Rinsing function is enabled in:
- Cooling mode
- H
0
0
3 -
P035
Default value must be set
0
0
255 s
P036
Setpoint setting
0 = Setpoint setting absolute
1 = Setpoint s/- 3K
1
0
1 -
P037
Display:
0 = No display
1 = Display of setpoint temperature
2 = Display of room temperature
3 = Display of sensor AI1
4 = Display of sensor AI2
5 = Display of sensor AI3
6 = Display of fan speed in %
0
0
6 -
P038
8 = Eco/Day mode changeover
26 = Eco/Day mode chan changeover
Heating/cooling via clip-on sensor
(2-pipe system)
72 = ON/OFF changeover
90 = ON/OFF chan Heating / cooling
changeover via clip-on sensor
(2-pipe system)
105
0
255 -
P039
Digital output V2:
0= No function
1= Heating requirement
2= Cooling requirement
3= Collective fault signal
1
0
3 -
P040
Valve actuation by means of pulse width modulation
0 = Function is disabled
1 = Function is enabled
0
0
1 -
P041
Reset time of PI controller to actuate the fan in
automatic fan mode
If P41=0 a PI controller is enabled.
Recommended reset time when using a
PI controller:
Reset time = 13 minutes
0
0
20 minutes
P042
Fan setting: Lock and released fan stages
3
0
127 -
P043
Digital input DI1
1
0
14 -
P044
Digital input DI2
2
0
14 -