4.13 H7 Troubleshooting
Digital display output
4.13.1
Description
4.13.2
Abnormal main circuit voltage.
Split stops running.
Error code is displayed on outdoor unit main PCB and user
interface.
Possible causes
4.13.3
Power supply voltage not within 90%~110% of rated voltage.
Outdoor unit main PCB is damaged.
Procedure
4.13.4
H7
Power supply voltage is not within
90%~110% of rated voltage
Yes
Provide normal power supply
No
Replace outdoor unit main PCB
Midea CAC Confidential