2.2 Hydronic box Piping
Figure 2-2.2: Hydronic box piping diagram
Legend
1
Water side heat exchanger
9
Water pump
2
Water flow switch
10
Manometer
3
Refrigerant liquid line temperature sensor
11
Safety valve
4
Refrigerant gas line temperature sensor
12
Refrigerant gas side
5
Water outlet temperature sensor
13
Refrigerant liquid side
6
Water inlet temperature sensor
14
Water outlet
7
Air purge valve
15
Water inlet
8
Expansion vessel
Key components:
1.
Air purge valve:
Automatically removes air from the water circuit.
2.
Safety valve:
Prevents excessive water pressure by opening at 43.5 psi (3 bar) and discharging water from the water circuit.
3.
Expansion vessel:
Balances water system pressure. (Expansion vessel volume: 8L.)
4.
Water flow switch:
Detects water flow rate to protect compressor and water pump in the event of insufficient water flow.
5.
Backup electric heater:
Provides additional heating capacity when the heating capacity of the heat pump is insufficient due to very low
outdoor temperature. Also protects the external water piping from freezing.
6.
Manometer:
Provides water circuit pressure readout.
7.
Water pump:
Circulates water in the water circuit.
1
2
3
4
5
6
7
8
10
11
12
13
15
9
14
F
14
202004
Midea CAC Confidential
Split
Summary of Contents for KMK-60RY1
Page 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Page 2: ...Split...
Page 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Page 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Page 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 113: ...Split...
Page 114: ...kaisai com...