4.2 E0, E8 Troubleshooting
Digital display output
4.2.1
Description
4.2.2
Water flow failure.
E0 indicates E8 has displayed 3 times. When an E0 error occurs, a manual system restart is required before the
system can resume operation.
Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes
4.2.3
The wire circuit is short connected or open.
Water flow rate is too low.
Water flow switch damaged.
Midea CAC Confidential
M thermal Split
202004
53
Procedure
4.2.4
E0 / E8
Water flow switch connection on
hydronic box main PCB is loose
1
Yes
Ensure the switch is connected properly
No
Water flow is insufficient
2
Yes
Check the water piping and valves. Make
sure the water piping is clean, there is no
air in the water piping and all valves are
open. If the internal circulator pump is
not already set to the highest speed,
increase its speed.
No
Water flow switch is damaged
Yes
Replace the water flow switch
No
Internal circulator pump can’t work
Yes
Turn off the power, check the wire in the
pump. Once that is done, the pump still
can’t work, replace the pump.
No
Replace hydronic box main PCB
Notes:
1. Water flow switch connection is port CN8 on the main PCB for hydronic box (labeled 9 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
2. Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figure 2-1.9 in Part 2, 1 “Hydronic Box
Layout”.
Midea CAC Confidential
Split
Summary of Contents for KMK-60RY1
Page 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Page 2: ...Split...
Page 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Page 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Page 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 113: ...Split...
Page 114: ...kaisai com...