4.24.4
C7
Power supply voltage of the unit is low.
Yes
Increase the power voltage to the
required range.
No
The space between the units is too
narrow for heat exchanger.
Yes
Increase the space between the units.
No
Heat exchanger is dirty or something is
block on the surface.
Yes
Clean the heat exchanger or remove the
obstruction.
No
Fan is not running.
Yes
Fan motor or fan is broken, change a new
fan or fan motor.
No
Water flow rate is low.
Yes
There is air in system or pump head is not
enough. Release the air and reselect the
pump.
No
Water outlet temp. sensor
1
is loosen or
broken.
Yes
Reconnect it or change a new one.
Notes:
1.
Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on
the hydronic box main PCB (labeled 10 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1.2 “Hydronic Box Layout” and to Table 4-5.3 in Part 4, 5.1 “Temperature Sensor Resistance
Characteristics”.
Midea CAC Confidential
Split
Summary of Contents for KMK-60RY1
Page 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Page 2: ...Split...
Page 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Page 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Page 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 113: ...Split...
Page 114: ...kaisai com...