M thermal Split
60
202004
Midea
M t
her
ma
l S
pli
t Ser
vice M
anual
4.6 E5, E6, E9, EA Troubleshooting
Digital display output
4.6.1
Description
4.6.2
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor
error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
4.6.3
Temperature sensor not connected properly or has malfunctioned.
Damaged outdoor unit main PCB.
Midea CAC Confidential
Split
Summary of Contents for KMK-60RY1
Page 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Page 2: ...Split...
Page 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Page 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Page 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Page 113: ...Split...
Page 114: ...kaisai com...