WARNING:
To comply with GR-1089 requirements, all intra-building copper cabling
used for SFP+, QSFP+, and QSFP28 ports must be shielded and grounded at both ends.
CAUTION:
Before router installation begins, a licensed electrician must attach a cable
lug to the grounding cables that you supply. See
“Connecting an MX10000 to Earth
. A cable with an incorrectly attached lug can damage the router.
Before connecting the router to earth ground, review the following information:
•
Two threaded inserts (PEM nuts) are provided on the lower rear of the chassis for connecting the router
to earth ground. The grounding points are spaced at 0.63 in. (16 mm) centers.
•
The grounding lug required is a Panduit LCD6-10A-L or equivalent (provided). The grounding lug
accommodates 6 AWG (13.3 mm²) stranded wire.If one or more JNP10K-PWR-DC2 power supplies are
installed in the chassis and set for high input (80-A), use the Panduit LCD4-14A-L or equivalent (provided).
This lug accommodates 4 AWG (21.1mm²) stranded wire.
•
The grounding cable that you provide for an MX10008 must be the same size or heavier than the input
wire of each power supply. Minimum recommendations are 6 AWG (13.3 mm²) stranded copper wire,
Class B; 90° C wire, or as permitted by local code.
SEE ALSO
JNP10K-PWR-AC Power Supply | 61
JNP10K-PWR-DC Power Supply | 65
Connecting AC Power to an MX10000 | 163
Connecting DC Power to an MX10000 | 164
MX10008 Transceiver and Cable Specifications
IN THIS SECTION
MX10008 Optical Transceiver and Cable Support | 119
MX10008 Cable Specifications for Console and Management Connections | 120
118
Summary of Contents for MX10008
Page 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Page 19: ......
Page 89: ......
Page 129: ......
Page 170: ......
Page 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Page 279: ......
Page 287: ......
Page 318: ...Restricted Access Warning 321 ...
Page 333: ...Jewelry Removal Warning 336 ...
Page 336: ...Operating Temperature Warning 339 ...
Page 345: ...DC Power Disconnection Warning 348 ...
Page 349: ...DC Power Wiring Sequence Warning 352 ...
Page 352: ...DC Power Wiring Terminations Warning 355 ...
Page 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...