Figure 111: Proper Load Balancing for JNP10K-PWR-AC2 Power Cables on MX100016
g100688
OR
12. For each power cable, insert the end of the cable with the Anderson connector into the
JNP10K-PWR-AC2 power supply module. The connector snaps and locks the cable into position.
WARNING:
Ensure that the power cords do not block access to router components
or drape where people can trip on them.
13. If the AC or DC power source outlets have a power switch, set them to the on (|) position.
14. Set the three dip switches to set the inputs and whether the power supply is running at 3000 W,
5000 W, or 5500 W. See
.
Set both enable switches to the on position when using both source inputs. When not using source
redundancy, set the unused source to the O (off) position. The LED turns red and indicates an error if
a source input is not in use and the enable switch is | (on).