Figure 28: Power Cord Retainer for an JNP10K-PWR-AC Power Supply
ON
FAULTPWR OKINP2
INP1
1 2
g050637
Each power supply connects to the power rail in the router. The power rail distributes the output power
produced by the power supplies to different router components. Each power supply provides power to
all the components in the router.
Each power supply has its own fan and is cooled by its own internal cooling system. Hot air exhausts from
the rear of the chassis.
SEE ALSO
JNP10K-PWR-AC Power Specifications | 105
How to Install a JNP10K-PWR-AC Power Supply | 196
How to Remove a JNP10K-PWR-AC Power Supply | 191
JNP10K-PWR-AC2 Power Supply
The JNP10K-PWR-AC2 power supply is a high-capacity, high-line model that is designed to support either
AC or DC systems in either a low power or high power mode. The power supply takes AC input and
provides DC output of 12.3 VDC, 5000 W with a single feed and 5500 W with a dual feed. For AC systems,
the operating input voltage is 180 to 305 VAC and for DC systems, the operating input voltage is 190 to
410 VDC.
The number of power feeds and whether the power supplies provides high or low output power is configured
using a set of dip switches on the faceplate of the power supply. If any power supply in the chassis is set
to low power, all power supplies are also set to low power, regardless of their dip switch settings. This
design is to prevent overloading of the power supply that is set to low power. See
for the settings for the dip switches.
63
Summary of Contents for MX10008
Page 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Page 19: ......
Page 89: ......
Page 129: ......
Page 170: ......
Page 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Page 279: ......
Page 287: ......
Page 318: ...Restricted Access Warning 321 ...
Page 333: ...Jewelry Removal Warning 336 ...
Page 336: ...Operating Temperature Warning 339 ...
Page 345: ...DC Power Disconnection Warning 348 ...
Page 349: ...DC Power Wiring Sequence Warning 352 ...
Page 352: ...DC Power Wiring Terminations Warning 355 ...
Page 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...