Page 48 of 49
20320 1S IPS R
Technical data
12 Technical data
Symbols
Must not be disposed of with household waste.
Rated voltage
AC 110 ... 240 V (± 10 %)
Mains frequency
50/60 Hz
Power loss
(max. load of all outputs)
max. 1.4 W
Efficiency
approx. 88 %
Rated voltage
DC 230 V (± 10 %)
Rated output
12 W
KNX
KNX medium
Bus output voltage
Output current
Short-circuit current
Parallel operation
with identical power supply
KNX connection
TP 256
DC 28 ... 31 V SELV
320 mA
max. 1 A
no
Connection terminal
IP communication
Ethernet 10/100 BaseT (10/100 Mbit/s)
IP connection
1 x RJ45
Ambient temperature
−5 ... +45 °C
Storage/transport temperature
−25 ... +75 °C
Relative humidity
max. 93 % (no moisture condensation)
Installation width
108 mm (6 rail units)
Connection mode:
Screw terminals
single wire
1 ... 4 mm²
stranded without ferrule
1 ... 4 mm²
stranded with ferrule
1 ... 2.5 mm²
13 Warranty
The warranty follows about the specialty store in between the legal framework as provided for by law.