Page 46 of 49
20320 1S IPS R
FAQ
9.3
Performing firmware update
The update has to be performed with the JUNG firmware update tool.
The JUNG firmware update tool can be downloaded from our website.
Detailed information about the JUNG firmware update tool can be found in the corresponding manual.
Fig. 30: Firmware update tool
•
Start JUNG firmware update.
• Enter physical address of device “Power supply with IP interface”.
•
Select update file with button “Update File”.
• Start update with button “Transmit”.
Update for both devices is performing automatically.
The update restores the default settings of both devices.
•
After the update assign physical address for both devices in device properties, see figure 5 and figure 7.
•
Download application program for both devices via “Download > Download Application”.
• Activate “Secure Commissioning” in device properties of the device “Power supply with IP interface”.
10 FAQ
Problem:
Power supply with IP interface - Additional functions:
Application download is canceled after timeout
Possible reason:
Physical address can’t be assigned at downloading.
Explanation:
The device has been inserted in the ETS project via copy and paste.
No addresses were assigned automatically.
All 8 tunnel addresses are in parking mode and invalid.
Solution:
Insert the device via drag and drop from the catalogue to the project.
The 8 tunnel addresses are assigned automatically by the ETS.