Advanced configuration
Telnet input
Description
stats
Shows various statistics on device and bus status
uptime: 114 days, 2:19
KNX communication statistics:
TX to IP (all)..: 333729 (ca. 233 t/m)
TX to KNX.......: 23244 (ca. 16 t/m)
RX from KNX.....: 94559 (ca. 66 t/m)
Overflow to IP..: 0
Overflow to KNX.: 0
TX tunnel re-req: 260
TP bus voltage..: 28.95 V
TX TP rate......: 50 T/s (= 100 %)
Uptime: Runtime of the interface since last restart
TX to IP (all): Number of all telegrams sent on IP
TX to KNX: Number of all telegrams sent on KNX
RX from KNX: number of telegrams received from the KNX bus
Overflow to IP: Number of telegrams that could not be sent to IP
Overflow to KNX: Number of telegrams that could not be sent to the KNX bus
TX tunnel re-req: Number of telegrams that had to be repeated in the tunnel
connections
TP bus voltage: Current bus voltage (at the time of calling stats)
TX TP rate: maximum telegram rate (TP)
free [clear]
Shows statistics about the memory usage
Used stack memory...: 14 %
Allocated memory....: 64 %
Unused memory.......: 35 %
TP-Tx buffer........: 0 %
TP-Tx buffer max....: 0 %
TP-Rx buffer max....: 0 %
Tunnel-T8 buffer max: 92 %
Used stack memory: Function stack utilization
Allocated memory: Allocated device memory
Unused memory: Unused device memory
TP-Tx buffer: Currently used TP send buffer
TP-Tx buffer max:Max. Utilization of TP send buffer (IP => TP) since system
startup
TP-Rx buffer max:Max. Utilization TP receive buffer (IP <= TP) since system
startup
Tunnel-XX (XX = 1..8) buffer max:Max. Utilization of the tunneling buffer. Only
tunnels whose buffer was used at all will be displayed
Clear the buffer statistics:
free clear