Page 22 of 49
20320 1S IPS R
Configuration
Function
Options
Description
Scene Welcome before
presence detection
active/inactive
When active, scene Welcome
will be activated by trigger 1. But
the scene will only be activated
when trigger 2 is not active during
activation of trigger 1, e.g. when no
presence is detected in the room
until this moment.
Activation time Welcome (s)
1 .. 30 .. 120
Duration for activated scene
Welcome. After this time the scene
of the extension scene (KO16)
changes from parameter “Output
value Welcome“ to parameter
“Output value if presence mode is
not active during that time“.
Output value (scene)
Welcome
1 .. 64
Value which is sent to the extension
scene (KO16) by activation of
scene Welcome.
Output value (scene) if
presence mode is not active
during that time (no presence
detected)
1 .. 64
Value which is sent to the extension
scene (KO16) after expiration of
scene Welcome.
Scene Presence after
presence detection
active/inactive
When active, scene Presence
will be activated by activation of
trigger 2. But the scene will only be
activated once after trigger 1 was
activated. This avoids retriggering
of scene Presence if the presence
detector changes his presence
status multiple times.
Output value (scene)
Presence
1 .. 64
Value which is sent to the extension
scene (KO16) by activation of
scene Presence.
Switching to operation
mode room controller after
presence detection
active/inactive
When active, operation mode of
room controller will be sent by
activation of trigger 2 according to
parameter “Output value (operation
mode)”.
Output value (operation
mode)
Automatic (0)/
Comfort mode
(1)/
Standby mode (2)/
Night mode (3)/
Frost/heat protection (4)
Value which is sent to operation
mode of room controller (KO32) by
activation of trigger 2.