2011-07-01/00561073 [SCR Power Controller TYA202]
91
8 Fault messages and alarms
M/S incompatible
#0002...0008
- Different software versions for master
and slave
- Different power controller types used
(max. load current, load voltage and
cascade controls (if applicable) do not
match)
Use same power controller
types with same software ver-
sions.
#0002
Different device software versions
Update devices to same soft-
ware versions
v
Service hotline
#0003
VDN numbers of devices do not match
Master/slave operation not pos-
sible
#0006
Different nominal voltages (device types)
of master and slave device.
Master/slave operation not pos-
sible
v
Chapter 1.3 „Order specifi-
cations“
#0007
Different nominal currents (device types)
of master and slave device.
#0008
Set cascade control of the master is not
compatible with that of the slave device.
Change cascade controls of
both devices to U or U
2
.
Teach-in
load monitoring!
Reminder that "manual" teach-in has
been configured but not yet executed.
Perform teach-in
v
Chapter 6.1 „Detection of
load faults“
Slave: limit value
Min. value reached
The value has gone below the set limit
value for the min. alarm.
Check why the value has gone
below the limit value.
Slave: limit value
Max. value reached
The set limit value for the max. alarm. has
been exceeded at the slave.
Check why the limit value has
been exceeded.
Slave: fault at
connected load
Break or short-circuit of a load resistor.
v
Chapter 6.1 „Detection of load faults“
Replace defective heating ele-
ments.
Slave:
Fuse breakage
(red LED fuse is lit)
1. Semi-conductor fuse defective
v
Chapter 8.2 „Replace defec-
tive semi-conductor fuse“
2. No voltage at terminal U1
- Check wiring
- Check the line fuse for the
load circuit
Slave:
SCR breakage
SCR defective
The device must be returned to
JUMO for repair.
h
Return the device
Slave: SCR
short-circuit
SCR defective
The device must be returned to
JUMO for repair.
h
Return the device
Error message
Cause
Remedy
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......