6 Special device functions
66
2011-07-01/00561073 [SCR Power Controller TYA202]
Overcurrent
The specifications in % refer to
load current changes
Temperature
coefficient (TC)
For heating elements with large positive or negative temperature coefficients it
is necessary to determine a suitable limit value yourself. It helps to monitor the
value of the current percentage deviation from the teach-in values. This value
is displayed in the operator level in the configuration window for the limit value
(Operator level
➔
Monitoring
➔
Limit value load monit.) in the bottom line:
Number of
heating ele-
ments
Star connec-
tion without
neutral conduc-
tor
Delta connection
6
-
-
5
10%
-
4
10%
10%
3
14%
13%
2
25%
26%
Example for 2
heating ele-
ments
L3
L2
L1
L3
L2
L1
H
No load monitoring takes place during the soft start phase (that can take longer
when current limiting is active) as the standard operating range of the load is not
yet reached. Teach-in cannot be performed in this phase either.
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......