5 Configuration
54
2011-07-01/00561073 [SCR Power Controller TYA202]
5.1.4
Set point value configuration
Here you can determine the analog input that specifies the set point value, how high
the base load should be and which alternative value is to be used in the event of a
fault.
Value/settings
Description
Default set point
value
Current input
This setting specifies which analog input is to supply the set
point value for the power output.
Voltage input
Binary input 1
Note:
This setting is only available when the controller
➔
SCR
control
➔
Logic (switch) is set.
In this case, the power controller is controlled like a solid state
relay (SSR) via binary input 1 or 2.
Contact: closed
➔
100% and open
➔
0%
(with factory-set control direction).
Binary input 2
Via interface
This means that the set point value for the power output is
provided via an interface.
Default value in the
event of a fault
Last value
The current, voltage and interface inputs are monitored for
faults/errors (line/wire breaks or bus errors). This setting is
used for specifying which alternative value is to be used by the
power controller if the default set point value is faulty.
The factory setting specifies use of the last valid value.
Voltage input
or cur-
rent input
Depending upon which input is set for the default set point
value, the second (still free) input appears at this point.
If a fault (e.g. line/wire break) occurs at the current input that is
factory set for the default set point value, the power controller
then uses the value at the voltage input.
Value, adjustable
This means that the "
Value in the event of a fault"
is used.
Value in the event
of a fault
000.0
This value is used in the event of a fault.
Maximum control
variable
0 ...
100
...115%
- of the maximum
load voltage,
- of the power
0 ...
100
%
- of the max. load
current
This setting is only available when the controller
➔
SCR con-
trol
➔
continuous (controller) is set.
The unit depends on the setting for cascade control and de-
vice type:
- for I, I
2
: 0 ...100 % of the max. load current, e.g.20A)
- for U, U
2
: 0 ... 115% of the max. load voltage e.g. 264.5V
- for P: 0 ...115% of the power 20A x 264.5V=5290W
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......