6 Special device functions
68
2011-07-01/00561073 [SCR Power Controller TYA202]
6.2 Manual mode
In this case, the set point value can be manually preset in % without the need
for external wiring via the analog input.
6.2.1 Default set point value in manual mode
Start
Manual mode, as set in the factory, can be accessed without entering a code.
h
Press the
key 1 x (manual mode)
h
Press the
key again
h
Increase or reduce the set point value with
or
The changes will immediately become effective at the load output and are indi-
cated on the display.
6.2.2 Configuring the teach-in (prerequisite for teach-in in manual mode)
The teach-in function records the current/voltage ratio of a load in the OK sta-
tus.
This function is not factory configured.
v
Configuration level See “Teach-in type, load monitoring” on page 57.
Configure
"manual"
teach-in
The power controller is in the level "Measured value overview".
h
Press the key
h
Set to Config.level
➔
Monitoring
➔
Load monitoring
➔
Undercurrent or
Overcurrent
➔
Teach-in type load monit.
➔
"manually“
h
Press the key
II
h
Press the
key 2 x
The device performs a reset.
If the teach-in is being performed for the first time, the message "Teach-in load
monitoring" appears in the bottom line of the display.
H
The set point value for manual mode is not saved in the event of a pow-
er failure!
After a power failure, the measured value overview is displayed.
Load voltage
Load current
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......