8 Fault messages and alarms
90
2011-07-01/00561073 [SCR Power Controller TYA202]
Supply voltage is
too low
Supply voltage is not within specified tol-
erance range
v
Chapter 10.1 „Voltage supply, load
current“
Check nominal voltage of the
device type
v
Chapter 1.3 „Order specifi-
cations“
Supply voltage is
too high
Supply voltage is not within specified tol-
erance range
Chapter 10.1 „Voltage supply, load cur-
rent“
Check nominal voltage of the
device type
Chapter 1.3 „Order specifica-
tions“
Temporary
drop in supply
Temporary equal proportion for trans-
former loads has been detected.
v
Ensure stable mains supply.
Master/Slave
rotary field error
Counterclockwise rotary field has been
detected
v
Master/Slave
incorrectly wired.
Wiring fault has been detected
Rotary field detec-
tion
failed
Rotary field detection not possible
- Check connection
v
Chapter 3.3 „Connection di-
agram“
- Eliminate line disturbances
Wire break
current input
Input current for the set measuring range
outside the valid range.
- Check wiring for wire breaks
and reverse polarity.
- Check upstream devices
(controllers)
Wire break
voltage input
Input current for the set measuring range
outside the valid range.
- Check wiring for wire breaks
and reverse polarity.
- Check upstream devices
(controllers)
Malfunction
bus error
No connection to the Profibus master
Check wiring and master device
(PLC).
Master/Slave
Error in comm.
Error in the data transfer between master
and slave
Check data connection of patch
cable
Data cable
faulty
Communication between master and
slave interrupted
Check the patch cables and, if
necessary, replace
Synchronization
failed
Slave device switched off or communica-
tion between master and slave interrupt-
ed
Check data connection of patch
cable or voltage supply
Error message
Cause
Remedy
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......