2011-07-01/00561073 [SCR Power Controller TYA202]
65
6 Special device functions
6.1 Detection of load faults
The load monitoring function can detect and signal a load failure, a partial load
failure or a partial load short circuit.
Undercurrent
This function is used for one or more heating elements connected in parallel
that are to be monitored for breakage.
Overcurrent
This function is used for several heating elements connected in series that are
to be monitored for short circuits.
Function
This function does not only take the decreasing or increasing load current into
consideration but also includes the load voltage in the monitoring process.
The correct load ratios of the system are saved during teach-in.
Based on this status, the load changes are continuously monitored irrespec-
tive of the required output level. In the event of a breakage or short circuit of a
heating element, the load current increases or decreases. This is detected by
the load monitor and a load fault is signaled.
Limit value
A limit value must be entered in the configuration or operator level in % for the
load monitor. This limit value depends upon the number of heating elements
connected in parallel or in series. For heating elements with a temperature co-
efficient TC
1 the limit value can be taken directly from the following tables:
Undercurrent
The specifications in % refer to
load current changes
Number
of heating
elements
Star connection
with separate
star points without
neutral conductor
Star connection with
common star points
without neutral con-
ductor
Delta connection
5
10%
-
-
4
13%
10%
-
3
17%
13%
10%
2
25%
20%
12%
1
50%
50%
21%
Example:
2 heating
elements
L3
L2
L1
L3
L2
L1
L3
L2
L1
Summary of Contents for TYA 202
Page 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Page 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Page 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Page 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Page 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Page 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Page 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Page 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Page 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Page 107: ......