11 Parameterization
64
11.4
Setpoint values
4 switchable setpoint values are assigned to a fixed-setpoint controller and can be entered on
the device or in the setup program.
The following table shows the setpoint changeover for fixed-setpoint controllers using two dig-
ital signals that can be set in Chapter 12.6.7 "Controller setpoint values", Page 97.
For program controllers
Ö
Chapter 8.1 "Entering program profiles", Page 49
11.4.1
Entering the values on the device
The setpoint values are entered in the parameter level.
Type
Signal 2 (Bit 1)
setpoint
changeover
Signal 1 (Bit 0)
setpoint
changeover
Setpoint value,
Controller 1
Setpoint value,
Controller 2
Fixed-setpoint
controller
0
0
Setpoint 1
Setpoint 1
0
1
Setpoint value 2
Setpoint value 2
1
0
Setpoint value 3
Setpoint value 3
1
1
Setpoint value 4
Setpoint value 4
Program control-
ler
W1 and W2 are predefined by the program
generator
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...