12 Configuration
Status after change of configuration
Modified parameters are incorporated immediately.
Behavior after power on
During the initialization phase of the controller module, the output signal adopts a value of 0 %
(in relation to the value range of the signal type).
Error handling
The behavior in the event of deviation above or below the measuring range (out of range) can
be configured. The settings made there also apply for probe/conductor breaks or probe/con-
ductor short-circuits. This results in a safe state for operation in the event of an error.
Error detection depends on the type of measuring probe (see technical data, measuring circuit
monitoring).
mea
s
ured value
s
tandard
s
ignal
for analog output
4 mA
20 mA
3,8 mA
20,5 mA
s
caling
s
tart
s
caling end
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...