12 Configuration
94
12.6.6
Output level monitoring
Output level monitoring monitors the output level in the corrected state. The output level must
be within a definable range around a mean output level. If it is not, an alarm is issued.
The alarm signal is available from the digital selector and can be processed further at any time.
Setup dialog box
Parameters
Parameter
Selection/settings
Description
Locking
Inactive
Output level monitoring generally not permitted
Active
Output level monitoring generally permitted
Determination time
0 s to 350 s to 9999 s
Calculation time for the mean output level
Output level band
0 % to 10 % to 100 %
Monitored output level band (admissible range
around the mean output level)
Alarm delay
0 s to 9999 s
Delay time for alarm triggering
Control differential
band
0 to 1 to 1999
Control differential band (admissible range
around the actual value in corrected state)
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...