107
12 Configuration
Position of hysteresis
Symmetrically
Here you can adjust the setting for which side the
hysteresis should be on.
Non-standard left
Non-standard right
Start-up alarm sup-
pression
Inactive
AF switching behavior is not suppressed
Active
AF switching behavior is suppressed, provided
that the value was not within the valid range.
Switch-On delay
0.0000 to 99999
Once the AF event has occurred, the time for the
switch-on delay begins to elapse.
The AF output remains unchanged at first until the
time set here has completely elapsed and the AF
event is relayed to the AF output.
If the AF actual value leaves the "bad range" dur-
ing this time for the switch-on delay, the count-
down begins again for each new limit value
violation.
Switch-off delay
0.0000 to 99999
Identical behavior as with switch-on delay, except
that the AF switch-off process is delayed. The
lock takes priority over the switch-off delay.
Pulse time
0.0000 to 99999
AF output is automatically deactivated after the
pulse time.
The output is only re-activated to the maximum
level via the set pulse time after repeated devia-
tion above or below the alarm values.
The lock takes priority over the pulse function.
Response at error
Off
AF output is switched off in the event of an error
On
AF output is switched on in the event of an error
Confirm
Off
The alarm function is automatically reset following
a limit value violation.
"Inactive" status
The lock can only be acknowledged if the AF
actual value is back in the valid range.
"Active" status
The lock can always be acknowledged if it has
been activated
Signal acknowledge-
ment
No selection
No acknowledgement possible
Digital selector
This signal acknowledges the lock.
Signal Locked
No selection
The "Signal Locked" input can be used to set and
maintain the output signal of the limit value moni-
toring function at the logical value "0".
As a result, alarms will be suppressed.
This means:
As long as "1" is applied at the input for "Signal
Locked", the output of the limit value monitoring
function will always be "0"
Digital selector
Additional functions Not selected (empty)
(setup only)
(
⎫
) Extension 1
Reserved functions for service
(
⎫
) Extension 2
(
⎫
) Extension 3
(
⎫
) Extension 4
Parameter
Selection/settings
Description
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...