77
12 Configuration
Linearization
Linearization is dependent upon the probe that is connected (measuring probe).
The predefined linearizations can be supplemented with
customer-specific linearization
.
Ö
Setup program:
S
ETUP
ONLY
> C
USTOMER
-
SPECIFIC
LINEARIZATION
Measuring value offset, measuring value factor
The value for the measuring value offset ensures a parallel shift of all measured values; the
value for the measuring value factor influences the slope of the values displayed.
Filter time const.
The filter time constant is used to adjust the digital input filter (2nd order filter). If the input signal
changes suddenly, approx. 26 % of the change is acquired following a period that corresponds
to the filter time constant (2× filter time constant: approx. 59 %; 5× filter time constant: approx.
96 %). A large filter time constant means: high attenuation of interference signals, slow reaction
of the actual value display, low limit frequency (low-pass filter).
Scaling start, scaling end
The maximum measuring range limits are displayed here, depending on the probe selected
and the linearization. These limits only affect the recording. If, for example, the scaling end for
a Pt100 is reduced from 850 °C to 400 °C, the recording only displays values up to 400 °C.
Measuring value off-
set
-100 to
0
to +100
Parallel shift of all measured values
Measuring value fac-
tor
1.000
Slope
Filter time const.
0 to
0.6
to 100
Time constant for adjusting the digital
input filter (0 s = filter off)
Scaling start
Default setting depends on sensor and linearization.
-99999 to +99999
Start value of display range for standard
signals
Scaling end
Default setting depends on sensor and linearization.
-99999 to +99999
End value of display range for standard
signals
Lead wire resistance 0
Ω
The line resistance for a two-wire circuit
is entered here.
ext. compensation
temp.
No selection
-
Analog selector
The measurand used to acquire the cold
junction temperature is set here.
fixed compensation
temp.
0 to 50 to 100 °C
If the cold junction has a fixed tempera-
ture, this is entered here.
KTY
at 25 °C/77 °F
0 to 2000 to 10000
Ω
Basic resistance of a KTY probe at
20 °C
Resistance measur-
ing range
0 to 400
Ω
These measuring ranges are available
for a resistance measurement with cus-
tomer-specific linearization
0 to 4000
Ω
Parameter
Selection/settings
Description
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...