19
3 Mounting
3.1
Mounting site and climatic conditions
The mounting site should be free from vibration, dust and corrosive media. Install controllers
as far away as possible from sources of electromagnetic fields, such as those created by fre-
quency converters or high-voltage ignition transformers. Conditions at the mounting site must
correspond to the following environmental influences:
3.1.1
Electrical data
3.1.2
Environmental influences
3.1.3
Housing
Voltage supply
Connection
Voltage
At the back via screw terminals
AC/DC 24 V +30/-25%, 48 to 63 Hz or AC 110 to 240 V +10/-15 %,
48 to 63 Hz
Power consumption
At voltage supply 230 V: max. 15 VA / 7 W
At voltage supply 24 V: max. 12 VA / 9 W
Inputs and outputs
Connection
Conductor cross section
At the back via screw terminals
Max. 2.5 mm
2
, wire or strand with end sleeve
Electrical safety
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Electromagnetic compatibility
Interference emission
Interference immunity
According to DIN EN 61326-1
Class A - For industrial applications only
Industrial requirements
Memory data recorder (1 recording image)
Memory cycle
Recording interval
When recording:
4 analog signals
3 digital signals
1 s
approx. 44 days
5 s
approx. 220 days
10 s
approx. 441 days
60 s
approx. 2646 days (7 years, 91 days)
Note:
In case of recording 2 recording images, the recording intervals are cut in an half
Ambient/storage temperature range
-5 to +55 °C/-30 to +70 °C
Resistance to climatic conditions
Humidity 3K3 (DIN EN 60721-3-3) with extended temperature
range,
rel. humidity
≤
95 % mid-year without condensation
Site altitude
Maximum 2000 m above sea level
Case type
Plastic front frame with metal case barrel (for indoor use)
Front frame dimensions
96 mm × 96 mm
Panel cut-out
92
+0.8
mm × 92+
0.8
mm according to DIN IEC 61554
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...