12 Configuration
124
Continuation
After the power failure, the program
continues to run from the point of dis-
ruption.
Start at actual value
After the power failure, the program
continues to run from the current actual
value.
In the event of an error
Continuation
Program continues to run.
Program stop
The time base of the program control-
ler is stopped.
Repetition
No
No program repeat
Yes
-
Regulate last setpoint value
No
-
Yes
Once the power is restored, the value
is set to the last setpoint value.
Start with power on
No
No automatic program start after power
on.
Yes
Automatic program start after power
on.
Adopt temp. changes
No
Do not adopt temporary changes.
Yes
Adopt temporary changes
Setpoint step
No
Yes
Gradient unit
Kelvin/minute
Kelvin/hour
Kelvin/day
Actual value input for tolerance
band monitoring
IN8 analog input 1
This value is monitored by the toler-
ance band.
Analog selector
Ö
Chapter 12.6.8 "Ramp function",
page 99
Signal for actual value 2
IN8 analog input 1
Analog selector
Program tolerance band
0 to 9999
Determines the distance of the toler-
ance band around the program profile.
0 means switched off.
The set value monitors the actual value
input for tolerance band monitoring set
above and checks whether it is follow-
ing the program setpoint. If it leaves
the tolerance band, the program flow is
stopped until the actual value is back
within the tolerance band.
Program end time
-1 to 0 to 9999
If -1 is entered, the program end time is
therefore infinite and the device does
not return to the operating loop. The
program end signal in the digital selec-
tor remains active until, for example,
another program is started.
Parameter
Selection/settings
Description
Summary of Contents for DICON touch
Page 2: ......
Page 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...
Page 36: ...4 Electrical connection 36...
Page 44: ...5 Operation 44...
Page 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...
Page 58: ...10 Functional level 58...
Page 66: ...11 Parameterization 66...
Page 150: ...12 Configuration 150...
Page 172: ...14 Special functions 172...
Page 180: ...15 Online parameters 180...
Page 182: ...16 Error and alarm messages 182...
Page 187: ...187 18 Approvals approval marks 18 1 GL...
Page 188: ...18 Approvals approval marks 188...
Page 189: ...189 18 Approvals approval marks...
Page 190: ...18 Approvals approval marks 190...
Page 191: ...191 18 Approvals approval marks...
Page 192: ...18 Approvals approval marks 192...
Page 193: ...193 18 Approvals approval marks 18 2 DIN...
Page 194: ...18 Approvals approval marks 194...