Viewing the assignment table:
⇨
Chapter 8.2.7 "Digital sensors", page 97
Manual linking:
⇨
Chapter "Procedure for manual linking of sensors", page 100
Configuring the inputs for digital sensors:
⇨
Chapter 10.10 "Digital sensors", page 29
The following table describes the startup procedure for an individual JUMO sen-
sor with digiLine electronics.
Step
Action
1
Log in as user "Master" or "Service" in order to have access to the
configuration in the device menu.
⇨
Chapter 8.2.1 "Logon/Logoff", page 91
2
Ensure that the serial interface being used for operation of digital
sensors is configured correctly. The protocol must be set to "Mod-
bus digital sensors".
3
Open the configuration of the digital sensors, select an available
output for digital sensors and enter the type information for the sen-
sor being connected.
Open the configuration of the digital sensors:
Device Menu > Configuration > Digital Sensors 1 to 6 > General
4
Open the assignment table for the digital sensors and check
whether an entry exists for the input for digital sensors that was just
configured. The line number must match the number of the input
for digital sensors and the assignment table entry must show the
status "Installation". The status is visualized by symbols in the right
column of the assignment table.
Open the assignment table:
Device Menu > Digital Sensors
⇨
Chapter 8.2.7 "Digital sensors", page 97
5
Connect the sensor with digiLine electronics to the bus.
6
Check whether the assignment table entry has changed from "In-
stallation" to "linked". If this is not the case after a waiting period of
about 10 seconds, linking has failed. In such a case, check the cor-
rectness of the configuration and bus cabling (see Chapter 21.1
"Troubleshooting and remedies for digital sensors", page 125). For
diagnosis, it is helpful to display more information about the assign-
ment table entry. To display the information, press the "Info" but-
ton. This opens a text window in which, among other things, the
most recent bus fault is displayed.
⇨
Chapter 8.2.7 "Digital sensors", page 97