15
139760_A GF 500 DV Oct. 2017
Figure 23.
Corner installation with 36” Snorkel termination.
Maximum horizontal run is 12”.
Snorkel Termination
This appliance is approved only for 36 inch Snorkel
termination.
Not approved for use with a 14 inch Snorkel.
The minimum horizontal run may be no less than 6”
(152 mm).
The maximum horizontal run may be no more than 24
in. (610 mm.)
One 45° Elbow may be used for a corner installation as
shown in fig. 23.
Exhaust Restriction:
Under normal circumstances, no
exhaust restriction is recommended. Keep the factory
setting (Position A - fully open).
Insulation Requirement:
Apply a minimum 1/2” thick
foil-faced ceramic insulation blanket behind the
Snorkel before attaching it to the wall (Jøtul PN 225606
is available).
Figure 21. Min./Max. vent required for horizontal termination.
Figure 22.
Min./Max. horizontal and vertical vent run 36” Snorkel
termination.