FORM 150.72-NM1 (1020)
147
JOHNSON CONTROLS
7
Unit Trip Volts
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the compressor and fan RLA’s
in the chiller.
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLA’s total 180A:
The programmed value will be 5.0V.
5V x 180A x 1.25 = 1125VA = 5.0V
225A
225A
* The minimum discharge pressure allowed is 235 PSIG. The Fan Differential Off Pressure High Limit will be lowered (reduced) to
prevent going below 235 PSIG based on where the fan control On Pressure is programmed.
When communications is required with a BAS or
OptiView Panel, individual unit IDs are necessary for
communications with specific chillers on a single RS-
485 line. ID 0-7 is selectable.
R E M O T E U N I T I D
P R O G R A M M E D = X
TABLE 11 – PROGRAM KEY LIMITS AND DEFAULT
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
325 PSIG
575 PSIG
570 PSIG
22.4 BARG
39.6 BARG
39.3 BARG
SUCTION PRESSURE CUTOUT
WATER COOLING
80.0 PSIG
120.0 PSIG
80.0 PSIG
5.52 BARG
8.27 BARG
5.52 BARG
GLYCOL COOLING
42.0 PSIG
70.0 PSIG
44.0 PSIG
2.9 BARG
4.83 BARG
3.03 BARG
LOW AMBIENT TEMP, CUTOUT
STANDARD
AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID TEMP
CUTOUT
WATER COOLING
—
—
36.0°F
2.2°C
GLYCOL COOLING
1.0°F
36.0°F
36.0°F
-18.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON PRESSURE
—
360 PSIG
485 PSIG
385 PSIG
24.8 BARG
33.4 BARG
26.5 BARG
FAN DIFFERENTIAL OFF PRESSURE
—
80 PSIG
160 PSID*
125 PSID
5.51 BARG
11.03 BARG*
8.62 BARG
TOTAL NUMBER OF COMPRESSOR
SINGLE SYSTEM
2
3
3
DUAL SYSTEM
4
6
6
NUMBER OF FANS PER SYSTEM
2
4
3
UNIT/SYSTEM TRIP VOLTS
CURRENT
FEEDBACK
0.5
4.5
2.5
REMOTE UNIT ID
—
0
7
0
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...