ELECTRICAL NOTES
1. Minimum Circuit Ampacity (MCA) is based on
125% of the rated load amps for the largest motor
plus 100% of the rated load amps for all other loads
included in the circuit, per N.E.C. Article 430-24. If
the optional Factory Mounted Control Transformer
is provided, add the following MCA values to the
electrical tables for the system providing power to
the transformer: -17, add 2.5 amps; -28, add 2.3
amps; -40, add 1.5 amps, -46, add 1.3 amps; -58,
add 1 amps.
2. The minimum recommended disconnect switch is
based on 115% of the rated load amps for all loads
included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated
load amps for the largest motor plus 100% of the
rated load amps for all other loads included in the
circuit to avoid nuisance trips at start-up due to lock
rotor amps. It is not recommended in applications
where brown outs, frequent starting and stopping of
the unit, and/or operation at ambient temperatures
in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated
load amps for the largest motor plus 100% of the
rated load amps for all other loads included in the
circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certi-
fied and maximum size is based on 225% of the
rated load amps for the largest motor plus 100% of
LEGEND
ACR-LINE
ACROSS THE LINE START
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT MOUNT CB
FACTORY MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON FUSED
RLA
RATED LOAD AMPS
S.P. WIRE
SINGLE POINT WIRING
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT
SWITCH)
LRA
LOCKED ROTOR AMPS
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-50 = 380/415-3-50
-58 = 575-3-60
VOLTAGE CODE
the rated load amps for all other loads included in
the circuit. Otherwise, HACR-type circuit breakers
must be used. Maximum HACR circuit breaker
rating is based on 225% of the rated load amps for
the largest motor plus 100% of the rated load amps
for all other loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum
and maximum wire size that can be accommodated
by the unit wiring lugs. The (2) preceding the wire
range indicates the number of termination points
available per phase of the wire range specified.
Actual wire size and number of wires per phase
must be determined based on the National Electri-
cal Code,
using copper connectors only
. Field
wiring must also comply with local codes.
7. A ground lug is provided for each compressor sys-
tem to accommodate a field grounding conductor
per N.E.C. Table 250-95. A control circuit ground-
ing lug is also supplied.
8. The supplied disconnect is a “Disconnecting
Means” as defined in the N.E.C. 100, and is in
-
tended for isolating the unit for the available power
supply to perform maintenance and troubleshoot-
ing. This disconnect is not intended to be a Load
Break Device.
9. Field Wiring by others which complies to the Na-
tional Electrical Code and Local Codes.
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...