FORM 150.72-NM1 (1020)
Maintenance
TABLE 30 – REAL TIME ERROR NUMBERS
ERROR NUMBER
(##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
TABLE 29 – VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
PROTOCOL
BACNET MS/TP
MODBUS RTU
5
YORKTALK 2
DE MODIFIER ADDRESS
0 TO 41943
(3)
1
-1
DE MODIFIER OFFSET
0 TO 99
(4)
0
N/A
P1 PROTOCOL
BACNET
N/A
N/A
P1 MANUAL MAC ADDRESS
0-127
(1)
N/A
N/A
P1 BAUD RATE
9600 TO 76800 OR AUTO
SELECTABLE
(1)
N/A
N/A
P1 PARITY
NONE
N/A
N/A
P1 STOP BITS
1
N/A
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127
(1)
N/A
P2 BAUD RATE
N/A
19,200
(2)
N/A
P2 PARITY
N/A
NONE
(2)
N/A
P2 STOP BITS
N/A
1
N/A
P2 HW SELECT BIT
N/A
RS-485 OR RS-232
(1)
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
P1 HW SELECT BIT
N/A
N/A
N/A
CHILLER ID
N/A
N/A
0
1
as required by network
2
or other as required by network
3
number is multiplied by 100, set as required by network
4
number is added to DE MODIFIER ADDRESS, set as required by network
5
unit operating software version C.MMC.13.03 or later required for Modbus protocol
The table below shows set-up requirements for each communication protocol.
The table below shows the real time error numbers that
may be encountered during communication setup and
a description of each.
REBOOT REQUIRED (CYCLE POWER)
AFTER SETTINGS ARE CHANGED.
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...