Table 2: Technical specifications
Type
Description
Bell circuit voltage and current
11.3 VDC to 12.5 VDC, maximum current 700 mA
continuous. For EN50131 Grade 2 applications, the voltage
rating is 9.6 VDC to 13.75 VDC.
Note:
The bell output supports continuous burglary alarms,
T3 fire alarms, and T4 CO alarms. Alarms sound in the follow-
ing priority: fire alarm, CO alarm, burglary alarm, and other
alarms.
Auxiliary power voltage and current.
Note:
AUX1 is used only for bur-
glary alarm initiating devices. AUX2
is used only for fire alarm initiating
devices such as smoke, heat, and
CO detectors.
11.3 VDC to 12.5 VDC, maximum current 700 mA shared
between the AUX1 and AUX2, CORBUS RED and BLK
terminals and PGM outputs. Ripple: 50 mVpp.
Note:
For EN50131 Grade 2 applications, the voltage rating
is 9.6 VDC to 13.75 VDC and the maximum current load is 430
mA.
PGM 1, 3, and 4 voltage and current 11.3 VDC to 12.5 VDC, 50 mA
PGM 2 voltage and current
11.3 VDC to 12.5 VDC, 300 mA
PG9HRDW8
Frequency band: 912.75 MHz to 919.106 MHz
Maximum power: 0.0447 W
RED, BLK, YEL, GRN
Corbus terminals, used to provide power and
communication between the converter and connected
compatible modules. Each compatible module
(keyapd, expander, power supply) has four Corbus
terminals that must be connected to the Corbus. 11.3 VDC
to 12.5 VDC, maximum current 700
mA shared between the AUX1 and AUX2 and PGM outputs.
Ripple: 50 mVpp.
Operating temperature
-10°C to 55°C (14°F to 131°F)
Note:
UL and ULC only verified operation for the range 0°C
to 49°C (32°F to 120°F).
Note:
The Converter and power supply are suitable for use
only inside the supervised premises.
Humidity
5% to 93% RH non-condensing.
Note:
UL and ULC only verified operation for a maximum of
93% RH.
Dimension
304mm x 396mm x 92mm (11.9" x 15.6" x 3.6")
Weight
2.85 kg (6.28 lb) including the battery
Note:
The PGM outputs are shared with the CORBUS RED and BLK terminals and the AUX
terminals.
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual
8