UL and ULC notes
The model PG9HRDW8 has been listed by UL and ULC for commercial burglary and residential
fire/burglary applications in accordance with the requirements in the Standards UL1610/UL1023/
UL985 and ULC-S304/ULC-S545. For UL/ULC installations, use this device only in conjunction with
compatible wireless receivers/control panels combination, model Qolsys IQPanel2 and IQPanel4.
Test the system weekly. Replace the standby battery every three to five years.
UL commercial and residential installation requirements and
considerations
UL commercial, UL household, and ULC security level I and II
burglar alarm unit
•
Power supply model SOY-1800222-NA (PGWLSHW40A) or HS40WPSNA or HS40WPSA shall be
employed.
•
One optional UL or ULC listed audible device rated to operate over the voltage range of 11.3
VDC to 12.5 VDC and rated 85 dB minimum.
•
One compatible Qolsys IQPanel2 with PowerG modem card.
•
All input zones shall be programmed as end of line supervised. For ULC Level II use DEOL
supervision.
•
Burglary initiating devices rated to operate over the voltage range of 11.3 VDC to 12.5 VDC.
•
All intrusion zones shall be programmed as audible.
•
The battery shall be used to provide a minimum back up power of four hours as per specific
application requirements
UL and ULC household fire warning system
•
Power supply model SOY-1800222-NA (PGWLSHW40A) or HS40WPSNA or HS40WPSAshall be
employed.
•
24 hour standby shall be provided.
•
At least one UL or ULC listed 4-wire latching type smoke detector rated to operate over the
voltage range 11.3 VDC to 12.5 VDC. A maximum smoke detector alarm load of 102 mA may
be employed on the 2-wire smoke detector circuit.
•
One DSC model RM-1 or RM-2 end of line supervision relay module.
•
One optional UL or ULC listed audible device, rated to operate over the voltage range 11.3
VDC to 12.5 VDC, with a maximum current rating of 700 mA and rated 85 dB minimum
as required for this application. The required bell cutoff time shall be a minimum of four
minutes for UL and five minutes for ULC. The local audible devices shall be programmed to
sound in a Temporal 3 pattern.
•
Model EOLR-2, for 4-wire smoke detectors, heat detectors, and CO detectors, and EOLR-3, for
2-wire smoke interface, end of line resistors shall be used.
•
For UL and ULC household fire warning systems, the fire alarm and CO detection devices shall
not be powered from the same AUX output as burglary alarm initiating devices.
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual
34