For fire detection installations that use smoke detectors, powered or non-powered heat detectors,
or CO detectors, use the wiring configuration on the right hand side of Figure 4. These devices
use separate AUX2 output for power. Make sure that the voltage range of the AUX2 output is
compatible with the input voltage range of the detector you are using.
Figure 4: SEOL wiring
Callout
Description
1
Zone terminal
2
COM terminal
3
Normally open contact
4
End-of-line resistor
5
Normally closed contact
Note:
Do not exceed a wire resistance of 100 Ω. For more information, see Table .
The following table shows the zone status for a given resistance value.
Table 6: SEOL zone status
Resistance
Description
Status
0 Ω
Shorted wire, loop shorted
Alarm
1 kΩ to 10 kΩ
Contact closed
Secure
Infinite
Broken wire, loop open
Alarm for burglary zones and
Trouble for fire zones
Double end-of-line resistors
If you use DEOL resistors at the end of a zone loop, the second resistor detects if a zone is in alarm,
tampered, or faulted. You can select DEOL supervision only if you are using normally closed devices
or contacts. You can use only one normally closed contact in each zone.
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual
14