Note:
Any zone programmed for fire or 24 hour supervisory must be wired with a SEOL
resistor regardless of the type of zone wiring supervision selected for the panel. If you change
the zone supervision from DEOL to SEOL, or from NC to DEOL, turn off the system completely
and then turn on the system for correct operation.
You can configure DEOL supervision through zone programming on the control panel.
For ULC Security Level II installations, use the wiring configuration in the following figure.
Figure 5: DEOL wiring
Callout
Description
1
Zone terminal
2
COM terminal
3
5600 Ω end-of-line resistor
4
Normally closed contact
Note:
Do not exceed a wire resistance of 100 Ω. For more information, see Table .
Note:
DEOL wiring is only for burglary use.
The following table shows the zone status for a given resistance value:
Table 7: DEOL zone status
Resistance
Description
Status
0 Ω
Shorted wire, loop shorted
Trouble
5600 Ω
Contact closed
Secure
Infinite
Broken wire, loop open
Tamper
11200 Ω
Contact open
Alarm
Wiring programmable outputs
You can use the programmable (PGM) outputs to activate devices such as LEDs and buzzers. To
wire an output to the PGM, complete the following steps:
1. Connect the positive wire from the device to the AUX+ terminal.
2. Connect the negative wire from the device to the PGM terminal.
15
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual