background image

 

Enabling Override Schedule (only appears when in 
Unoccupied Mode) 

The override schedule prompt only appears when the 
thermostat is in the unoccupied state. This menu 
selection gives the user the option of overriding the 
unoccupied setpoints with the occupied setpoints at 
the local user interface for the amount of time specified 
under the 

Establishing the Temporary Occupancy 

Time (ToccTime)

 parameter (see 

Configuring the 

TEC2104-1

 section). 

To override the unoccupied state while in the Main 
User Menu: 

1. 

Answer NO to all prompts until the Override 
Schedule prompt appears. If the thermostat is in 
the unoccupied state, this is the first prompt. 

2. 

Press YES to enable the temporary override. The 
TEC2104-1 returns to the Status Display Menu. 

When scrolling through the Status Display Menu, 

Override

 now appears for the schedule status 

parameter. 

Resuming the Programmed Schedule (only 
appears when in the Override Mode) 

To resume the schedule while in the Main User Menu: 

1. 

Answer NO to all prompts until the Resume 
Schedule prompt appears. If the thermostat is in 
the override state, this is the first prompt. 

2. 

Press Yes to resume the programmed schedule. 

The TEC2104-1 returns to the Status Display Menu. 

Entering Temperature Setpoints 

The first prompt appearing in the Main User Menu of 
the TEC2104-1 sets the temperature setpoints. This is 
where all heating and cooling setpoints for the 
occupied and unoccupied states are entered. It is also 
where any temporary setpoints are entered. 

To enter the heating and cooling setpoints for the 
occupied and unoccupied modes (permanent or 
temporary), follow the steps in Table 4. When 
changing the temperatures, pressing the keys once 
changes the temperature 0.5 F/C

°

 and holding down 

the keys changes the temperature by 5 F/C

°

 

increments. 

Setpoint Type 

Permanent Setpoints

 are permanently stored in the 

programmed schedule. This is the default setpoint 
type. 

Note: 

Permanent setpoints revert to the 

programmed N2 network settings with each change of 
schedule status. 

Temporary Setpoints

 are changed, but are in effect 

only for the time specified in the 

Establishing the 

Temporary Occupancy Time (ToccTime)

 parameter 

(see the 

Configuring the

 

TEC2104-1

 section). 

Note: 

There is no indication that a temporary 

setpoint is enabled or active. 

After the specified temporary occupancy time elapses, 
the temporary setpoint reverts to the permanent 
setpoint. 

The temporary setpoint can be cancelled at any time 
by using the Permanent Setpoint option in this menu. 
When permanent modifications of the setpoints are 
required, this parameter needs to be set to permanent. 

Notes:

 

If a setpoint is overridden over the N2 

network, it appears the setpoint value can be changed 
through the TEC2104-1, but the setpoint is actually still 
held at the overridden value. 

If the heating and cooling setpoints are overridden 
over the N2 network such that the deadband is 
violated, the TEC2104-1 automatically changes one of 
the setpoints to maintain the deadband. 

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

15

 

Summary of Contents for TEC2104-1

Page 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Page 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Page 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Page 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Page 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Page 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Page 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Page 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Page 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Page 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Page 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Page 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Page 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Page 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Page 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Page 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Page 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Page 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Page 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Reviews: