Table 2: Installer Configuration Menu (Cont.)
Sets the Minimum Heating/Cooling
Deadband
Default:
2.0
°
F (1.1
°
C)
See the
Setting the Heating/Cooling
Deadband (Deadband)
section
.
Determines How the Fan Activates in
Response to a Call for Heat
Default: Thermostat Controls Fan
(On)
See the
Setting the Fan Control
(Fan cont)
section.
Delays Fan Termination at Cycle’s End
for 60 Seconds
Default: No Delay
(Off)
See the
Setting the Fan Delay
(Fan del)
section
.
Sets the N2 Address
Default:
253
See the
Setting the N2 Address
(N2 addr)
section
.
Sets the Duration for Temporary
Occupancy Time
Default: Three Hours
(3.0 hrs)
See the
Establishing the Temporary
Occupancy Time (ToccTime)
section
.
Room Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the
Room Air Sensor Calibration
(Cal RS)
section
.
Auxiliary/Outdoor Air Sensor
Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the Auxiliary
Temperature/
Outdoor Air Sensor
Calibration (Cal OS)
section
.
Disable/Enable Second Heating Stage
Default:
Two Stages
See the
Disable/Enable Second
Heating Stage (H Stage)
section
.
Disable/Enable Second Cooling Stage
Default:
Two Stages
See the
Disable/Enable Second
Cooling Stage (C Stage)
section
.
Disables Heating Operation based on
Auxiliary/Outdoor Air Temperature
Default:
120
°
F (49
°
C)
See the
Setting the Heating Lockout
(H lock)
section
.
Disables Cooling Operation based on
Outdoor Air Temperature
Default:
-40
°
F (-40
°
C)
See the
Setting the Cooling Lockout
(C lock)
section
.
Sets the Economizer Changeover
Temperature
Default:
55
°
F (13
°
C)
See the
Setting the Economizer
Changeover Temperature (Chngstpt)
section
.
Sets the Outdoor Air Damper Minimum
Position
Default:
0%
See the
Setting the Outdoor Air
Damper Minimum Position (Min pos)
section
.
Sets the Mechanical Cooling Mode
Default:
Off
See the
Setting the Mechanical
Cooling Mode (C mech)
section
.
Sets the Mixed Air Temperature
Setpoint
Default:
55
°
F (13
°
C)
See the
Setting the Mixed Air
Temperature Setpoint (Mix stpt)
section.
Displays the Mixed Air Temperature
Default:
N/A
See the
Displaying the Mixed Air
Temperature (Display)
section
.
Deadband
set? Y/N
C Stage
set? Y/N
Fan cont
set? Y/N
H lock
set? Y/N
Fan del
set? Y/N
C lock
set? Y/N
N2 addr
set? Y/N
Chngstpt
set? Y/N
ToccTime
set? Y/N
Min pos
set? Y/N
Cal RS
set? Y/N
C mech
set? Y/N
Cal OS
set? Y/N
Mix stpt
set? Y/N
H Stage
set? Y/N
Display
MS? Y/N
8
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions